![](https://berg-energie.de/wp-content/uploads/2023/10/LoRaWAN_Gateway-1024x1024-1.jpg)
LoRaWAN-Gateway Outdoor
The LoRaWAN gateway is designed for outdoor use and enables the wireless connection of LoRaWAN sensors (nodes). The gateway contains SX1301 + 2x 1257 LoRaWAN concentrators which offers 10 programmable parallel demodulation paths.
- Connection of LoRaWAN sensors
- SX1301 LoRaWAN concentrator
- Protection class IP65
- Incl. Fiber optic antenna
Characteristics
Technical data
Radio frequency | 868 MHz |
Power supply | PoE or external power supply 230/12 VDC |
Antenna | external fiber optic antenna for LoRa RF |
Connection | TCP/IP (RJ 45) |
Protection class | IP 65 Outdoor-Gateway |
Dimensions in mm (H x L x W): | 490 x 120 x 190 |
Variants and tender texts
LoRaWAN-Gateway Outdoor Item number: 004900
Radio frequency: 868 MHz
Power supply: PoE or external power supply 230/12 VDC
Antenna: external fiber optic antenna for LoRa RF
Connection: TCP/IP (RJ 45)
Protection class: IP 65 outdoor gateway
![](https://berg-energie.de/wp-content/uploads/2023/10/BCM4-300x300-1.jpg)
BCM 4 M-Bus
For the combined recording of 4 S0 pulse counters and machine running times. The multiocounter module is designed for data transmission in the M-Bus format.
- Counter module with 4 separate S0 channels according to EN 62053-31
- Communication variant: M-Bus
- DIN rail mounting according to IEC 60715
- 3 TE width
- Suitable for contacts and open collector transistors
- Channels for counting machine running times can be programmed
Characteristics
Technical data
Case | according to DIN 43880, material PPO self -extinguishing |
Dimensions | W: 53 mm (3TE), H: 90 mm (including connector), D: 58 mm |
Assembly | on DIN rail according to EN 50022 |
Protection class | IP20 |
Connections | S0 inputs: 1 x 8 pin. Screw plug-in terminals, pitch 5.08, bus: 2 x 2-pole. Screw-in terminals, pitch 3.81 |
Supply | 24 VDC +/- 5 % |
Current consumption | max. 60 mA |
Inputs | 4 x S0 Klasse A nach EN 62053-31 |
S0 voltage | 15.5V idle |
S0 line current | 4 x ca.14 mA max. |
Active | Input IS0 >10mA |
Inactive input | IS0 < 2mA |
Debounce time | ca. 8 msec |
Temperature range | -10 °C bis -55 °C |
Baud rates | 300, 2400, 9600 Bit/s (Default: 2400 Bit/s) |
Bus load | 1 unit load (approx. 1.5mA) |
Number of logical 4M bus slaves | 4 |
Slave function | 4 x counters, 32bit dual |
Max. Counting frequency | 50Hz |
Data transfer | M-Bus according to EN 1434 |
Variants and tender texts
BCM 4 M-Bus Item number: 003773
and conversion of the pulse levels into the M-Bus protocol
![](https://berg-energie.de/wp-content/uploads/2023/10/BCM8-M-Bus-frontal-401x300-1.jpg)
BCM 8 M-Bus
For the combined recording of 8 S0 pulse counters and machine running times. The multiocounter module is designed for data transmission in the M-Bus format.
- Counter module with 8 separate S0 channels according to EN 62053-31
- Communication variant: M-Bus
- DIN rail mounting according to IEC 60715
- 6 TE width
- Suitable for contacts and open collector transistors
- Channels for counting machine running times can be programmed (depending on the model)
Characteristics
Technical data
Case | according to DIN 43880, material PPO self -extinguishing |
Dimensions | B: 106 mm (6TE), H: 115 mm (inkl. Steckverbinder), T: 63 mm |
Assembly | on DIN rail according to EN 50022 |
Protection class | IP20 |
Connections | S0 inputs: 2 x 8 pin. Screw plug-in terminals, pitch 5.08, bus: 2 x 2-pole. Screw-in terminals, pitch 3.81 |
Supply | 24 VDC +/- 5% |
Current consumption | max. 350 mA bei 24VDC |
Inputs | 8 x S0 Class A according to EN 62053-31 |
S0 voltage | 18V idle |
S0 line current | 8 x ca.17 mA max. |
Active input | IS0 > 10mA |
Inactive input | IS0 < 2mA |
Debounce time | ca. 8 msec |
Temperature range | -10 °C bis -55 °C |
Baud rates | 300, 2400, 9600 Bit/s (Default: 2400 Bit/s) |
Bus load | 1 unit load (approx. 1.5mA) |
Number of logical 4M bus slaves | 4 |
Slave function | 8 x Counter, 32Bit dual |
Variants and tender texts
BCM 8 Modbus Item number: 002639
and conversion of the pulse levels into the Modbus RTU protocol
![](https://berg-energie.de/wp-content/uploads/2023/10/BCM8-DP-frontal-401x300-1.jpg)
BCM 8 Modbus
For the combined recording of S0 pulse counters and machine running times. The multicounter module is designed for data transmission in the ModbusRTU protocol.
- Counter module with 8 separate S0 channels according to EN 62053-31
- Communication variant: ModbusRTU
- DIN rail mounting according to IEC 60715
- 6 TE width
- Suitable for contacts and open collector transistors
- Channels for counting machine running times can be programmed (depending on the model)
Characteristics
Technical data
Case | according to DIN 43880, material PPO self -extinguishing |
Dimensions | B: 106 mm (6TE), H: 115 mm (inkl. Steckverbinder), T: 63 mm |
Assembly | on DIN rail according to EN 50022 |
Protection class | IP20 |
Connections | S0 inputs: 2 x 8 pin. Screw plug-in terminals, pitch 5.08, bus: 2 x 2-pole. Screw-in terminals, pitch 3.81 |
Supply | 24 VDC +/- 5% |
Current consumption | max. 350 mA bei 24VDC |
Inputs | 8 x S0 Class A according to EN 62053-31 |
S0 voltage | 18V idle |
S0 line current | 8 x ca.17 mA max. |
Active input | IS0 > 10mA |
Inactive input | IS0 < 2mA |
Debounce time | ca. 8 msec |
Temperature range | -10 °C bis -55 °C |
Baud rates | 300, 2400, 9600 Bit/s (Default: 2400 Bit/s) |
Bus load | 1 unit load (approx. 1.5mA) |
Number of logical 4M bus slaves | 4 |
Slave function | 8 x Counter, 32Bit dual |
Max. Counting frequency | 50Hz |
Data transfer | S0 / machine runtimes on ModbusRTU |
Data formats | DWORD (32 bit dual), real single precision |
Baud rates | 300 … 57.6k |
Transmission media | RS485, connection via screw terminals |
Termination | Fail Save, can be switched on/off via jumper |
Variants and tender texts
BCM 8 Profibus DP Item number: 000595
and conversion of the pulse levels into the Profibus DP protocol
![](https://berg-energie.de/wp-content/uploads/2023/10/BCM8-DP-frontal-401x300-1.jpg)
BCM 8 DP
S0 pulse acquisition module for transmitting consumption values from up to 8 intermediate meters into the Profibus DP protocol
- Counter module with 8 separate S0 channels according to EN 62053-31
- Communication variant: Profibus DP
- DIN rail mounting according to IEC 60715
- 6 TE width
- Suitable for contacts and open collector transistors
- Channels for counting machine running times can be programmed (depending on the model)
Characteristics
Technical data
Case | according to DIN 43880, material PPO self -extinguishing |
Dimensions | B: 106 mm (6TE), H: 115 mm (inkl. Steckverbinder), T: 63 mm |
Assembly | on DIN rail according to EN 50022 |
Protection class | IP20 |
Connections | S0 inputs: 2 x 8 pin. Screw plug-in terminals, pitch 5.08, bus: 2 x 2-pole. Screw-in terminals, pitch 3.81 |
Supply | 24 VDC +/- 5% |
Current consumption | max. 350 mA bei 24VDC |
Inputs | 8 x S0 Class A according to EN 62053-31 |
S0 voltage | 18V idle |
S0 line current | 8 x ca.17 mA max. |
Active | Input IS0 >10mA |
Inactive input | IS0 < 2mA |
Debounce time | ca. 8 msec |
Temperature range | -10 °C bis -55 °C |
Baud rates | 300, 2400, 9600 Bit/s (Default: 2400 Bit/s) |
Bus load | 1 unit load (approx. 1.5mA) |
Number of logical 4M bus slaves | 4 |
Slave function | 8 x Counter, 32Bit dual |
Max. Counting frequency | 50Hz |
Data transfer | S0 on ProfibusDP |
Data interface | Profibus DP, SUB-D 9pol. According to EN 50170, |
Baud rates | up to 12 Mbaud |
DP assignment | 32 bytes E-periphery, 32 byte A-periphery |
Variants and tender texts
BCM 4 M-Bus Item number: 003773
and conversion of the pulse levels into the M-Bus protocol
![](https://berg-energie.de/wp-content/uploads/2023/10/BIP-IV.jpg)
BIP IV Modul
The BIP IV is an intelligent gateway and enables the UBN series measuring devices, BME energy meters and devices with Modbus RTU protocol to be connected to the Profibus. The interface has a Profibus-DP standard interface according to EN50170 based on the intelligent Profibus controller SPC3 as well as another RS485 interface, the device bus.
- Profibus gateway for connecting devices from the UBN series and energy meters from the BME series via Modbus RTU
- Sub-networking of up to 32 Modbus participants possible
- Communication variant: Profibus DP
- DIN rail mounting according to IEC 60715
- 3 TE width
Characteristics
Technical data
Case | Insulated plastic housing for mounting on DIN rails of type DIN EN 50022 (TS35) |
Protection class | IP 20 for front panel and IP 20 for terminals |
Temperature range | Ambient temperature – 10°C to 55°C |
Storage temperature – 20°C to 60°C | |
Supply | 24 VDC +/- 5% / 50mA |
Connection elements | Screw terminals (type K) for conductors up to 4 mm2 according to VDE 0100 and VGB 4 |
Weight | ca. 80g |
Interfaces | Profibus SUB-D 9pol. according to EN 50170, baud rates up to 12MBit/s
RS 485 (device bus) for measuring device connection The interfaces are electrically isolated from each other |
Occupancy of the decentralized peripherals | 32 bytes inputs, 32 bytes outputs |
Transfer rates | 9600 bit/s for devices type code 1-5
19200 bit/s bit/s for devices type code 6 (Modbus RTU) and type code 7 (meter BME) |
Variants and tender texts
BIP-MANAGER V4 Item number: 002694
S7-300/400 controller for reading out measurement data
of the mountain measuring devices connected to BIP IV
BIP-MANAGER TIA Item number: 004385
S7-1200/1500 controller for reading out measurement data
of the mountain measuring devices connected to BIP IV
BIP IV Modul Item number: 004356
for integrating BME Modbus meters
or UBN network analyzers
Siemens Profibus DP
![](https://berg-energie.de/wp-content/uploads/2023/10/BAC2-frontal.jpg)
BAC2 analogue counter
The BAC2 module is a 2-channel high-resolution measuring module for analog values and designed for passive 2-wire measuring transducers 4-20mA (flow, temperature, humidity, pressure, level, etc.) or active measuring signals 0(4)-20mA. When using passive 2-wire transmitters, the measuring transducers are supplied by the BAC2.
- High measurement resolution (measuring interval 200ms with a resolution of 15 bits)
- Energy values are saved in the EEPROM in the event of a power failure
- Data communication: Modbus RTU
- Parameterization is carried out using the editor integrated in BAC2
- DIN rail mounting according to IEC 60715
- 3 TE width
Characteristics
Technical data
Case: | Insulated plastic housing for mounting on DIN rails of type DIN EN 50022 (TS35) |
Protection class: | IP 20 for front panel and IP 20 for terminals |
Dimensions: | W:53 mm (3TE), H:90 mm, D:58 mm (without Profibus plug) |
Supply: | 24VDC +/- 5% ca. 100mA |
Connection elements: | Screw terminals for conductors up to max. 4 mm2 |
Weight: | ca. 90g |
Analog inputs: | 2, electrically isolated, but not from each other |
Measuring range: | 2 x 0(4)-20mA |
Internal burden: | 102.4 ohms, adjustable |
Sensor supply: | approx. 22V channel, current limited to 27..28mA (short-circuit proof) |
Resolution: | 15Bit (32767 counts), standardized to 0..10000 by software |
Samplerate: | 5 / sec |
Nonlinearity: | 10ppm Full Scale Range |
Temperature drift: | -13ppm/°C, measured in the ambient temperature range 20-50°C |
Energy meter: | 2 x 32Bit |
Real time clock: | batteriegepuffert, Genauigkeit 3,5ppm |
Load profile memory: | Memory size 4 megabytes, sufficient for approx. 262,000 records |
Data interface: | RS485, Modbus RTU protocol |